Copy link

Height difference should be calculated as the "difference between the midpoint of the lower opening and the neutral pressure level". For a typical door or casement type window, assuming neutral pressure level as one half the door/window height, this renders the height difference as 1/4 the total door/window height. Reference ASHRAE Handbook of Fundamentals chapter 16 equation 46.

Height difference should be calculated as the "difference between the midpoint of the lower opening and the neutral pressure level".  For a typical door or casement type window, assuming neutral pressure level as one half the door/window height, this renders the height difference as 1/4 the total door/window height.  Reference ASHRAE Handbook of Fundamentals chapter 16 equation 46.